Installed a Missing Defrost Timer on a Frosted Walk-In Cooler at a Waco Nursing Home 09.16.26
Clay · September 16, 2026 · Near Owen Lane, Waco TX 76710

A Waco nursing home called when its walk-in cooler went down with the evaporator coil frosted over. Clay confirmed the solenoid was functioning and cycling the unit off, then traced the frost to a missing control: the system had no defrost timer installed. With nothing scheduling defrost periods, ice kept building on the coil until the box could no longer hold temperature. A new defrost timer was installed and set for four defrost periods a day, and the cooler came back online and cooling properly. An estimate has been submitted to replace a door and a fan blade. For walk-in cooler service in Waco, call 254-272-2714. Texas TACLA89963C, R290 Certified, factory authorized for Norlake and Master-Bilt.