Replaced a Grounded Compressor on a Clifton Restaurant AC Unit
Clay · August 4, 2026 · Near West 5th Street, Clifton TX 76634

A Clifton restaurant lost cooling on a packaged air conditioning unit after the breaker tripped and would not hold on a call for cooling. Lead technician Clay ran an insulation resistance test at the compressor terminals and confirmed the motor windings had grounded to the housing, a failure with no repair path. He recovered the refrigerant, removed the compressor, contactor, run capacitor and filter/drier, and replaced all four. The system was evacuated, recharged with virgin R-410A, and verified in operation before he left. For commercial HVAC service across the Heart of Texas, call 254-272-2714. Texian Cold is licensed Texas TACLA89963C and R290 Certified.