Walkin floral cooler not holding temperature. Fans running and calling for cool…

Clay Kerr · January 30, 2026

Walkin floral cooler not holding temperature. Fans running and calling for cooling. Examined condenser. Found unit low on charge, head pressure fan control not

Walkin floral cooler not holding temperature. Fans running and calling for cooling. Examined condenser. Found unit low on charge, head pressure fan control not set properly, pitted contactors and wrong sized refrigerant filter/drier. Added 6 lbs of R404a and adjusted fan control. Filter and contactor needs replaced.